Specifications
For Flow Service - Setpoint Range:
0.01 to 3.0 fps [0.003 to 0.9 mps]
- Hydrocarbon-based Liquids:
0.01 to 5.0 fps [0.003 to 1.5 mps]
0.25 to 120 sfps [0.08 to 37 smps] at standard conditions of 70° F [21.1° C] and 14.7 psia [1.013 bar(g)].
Accuracy: (whichever reading is higher)
- Liquids: ± 0.5% reading or ± 0.04 fps [± 0.012 mps]
- Gases: ± 0.5% reading or ± 2 sfps [± 0.06 nmps]
For Temperature Service:
Accuracy: ± 2° F [±1° C]
Repeatability: ± 1° F [± 0.6° C]
Response Time: As low as 3 seconds.
Enclosure: NEMA 4X/IP66 Rated. Standard: Polyester powder coated aluminum, with single 1" NPT conduit port. Optional: Stainless steel. Optional: Dual-conduit port, aluminum with 1/2" NPT or M20 metric conduit ports.
Compliances and Agency Approvals: FM, FMc, ATEX, IECEx, EAC/TR CU, Inmetro. EQM/UCAS, CE mark. PED, CRN. (UKCA, UKEX pending)
Meets EC directives for EMC and LVD. Probe complies with Canadian Electrical code requirements of ANSI/ISA 12.27.01-2011 as a single seal device.
FM/FMc: |
XP, Class 1, Div. 1 Groups B,C,D, T3A or T4 Ta ≤60°C
DIP, Class II/III, Div. 1, Groups E,F,G, T3A or T4 Ta ≤60°C
Nonincendive for Class I, II and III, Division 2, Groups A,B,C,D,E,F, and G, T3A or T4 -40°C ≤Ta≤60°C; hazardous (classified) locations, indoors and outdoors.
Type 4X |
ATEX: |
Integral: II 2 G Ex db IIC T4…T2 Gb
II 2 D Ex tb IIIC T135°C…T300°C Db
Remote enclosure
+ electronics: II 2 G Ex db IIC T6 Gb
II 2 D Ex tb IIIC T85°C Db
Local enclosure
+ sensor II 2 G Ex db IIC T4…T1 Gb
II 2 D Ex tb IIIC T135°C…T345°C Db
Pigtail version II 2 G Ex db IIC T4…T3 Gb
II 2 D Ex tb IIIC T135°C…T200°C Db
|
IECEx
(EQM/ECAS): |
Integral: Ex db IIC T4…T2 Gb
Ex tb IIIC T135°C…T300°C Db
Remote enclosure
+ electronics: Ex db IIC T6 Gb
Ex tb IIIC T85°C Db
Local enclosure
+ sensor Ex db IIC T4…T1 Gb
Ex tb IIIC T135°C…T345°C Db
Pigtail version Ex db IIC T4…T3 Gb
Ex tb IIIC T135°C…T200°C Db |
Optional N.I.S.T. Flow Calibration Services
Factory N.I.S.T. calibration in air or water is available as an option for customer specified setpoint(s) or a flow curve based on the media ranges specified above.
Flow Element
Materials of Construction: All welded 316L stainless steel for all wetted surfaces.
Process Connection:
- Standard: 0.75 inch male NPT
- Optional: 1 inch male NPT, flanges or retractable sensing element.
Insertion Length:
- 1.2 inch [30 mm]
- 2 inches [51 mm]
- 4 inches [102 mm]
- 6 inches [152 mm]
- 9 inches [229 mm]
- 12 inches [305 mm]
- 18 inches [457 mm]
Customer specified lengths are available as an option.
Operating Temperature:
- Standard: -40° to +350° F [-40° to +177° C]
- Optional: -100° to +500° F [-73° to +260° C] or -100° to +850° F [-73° to +454° C]
- Operating Pressure: To 3500 psig [240 bar(g)]
Control Circuit
Operating Temperature: -40° to +140° F [-40° to +60° C]
Universal AC/DC supply. Input terminals and jumpers on circut board select specific power.
AC |
108-132V |
13W, 100mA max. |
AC |
207-253V* |
14W, 50mA max. |
AC |
18-28V |
7W, 230mA max. |
DC |
21-30V |
7W, 230mA max. |
* AC mains preset by factory: FM & FMc as 108-132 Vac; All others as 207-240 Vac
Relay Contacts: Field configurable dual SPDT or single DPDT rated 6 amps at 115 Vac, 240 Vac or 24 Vdc.
Output Signal: Analog DC voltage related to flow or level/interface signal and proportional to temperature.
Electrical Connection: 1 inch female NPT
Remote Configuration: Available as an option with customer specified interconnecting cable length.