Specifications
- Materials of Construction (Wetted Parts)
316L SS with Hastelloy C-22 thermowells
- Flow Sensitivity/Setpoint Range
Water: 0.01 FPS to 0.5 FPS [0,003 MPS to 0,15 MPS]
Air/Gas: 0.25 FPS to 400 SFPS [0,076 MPS to 122 MPS]
- Repeatability: ±0.5% of reading
- Temperature Coefficient For temperatures > ±30°F [±16°C]
Gas: Maximum ±0.025% of reading/°F up to 250°F [±0,05% of reading/°C up to 121°C]
Liquid: Maximum ±0.2% of reading/°F up to 250°F [±0,367% of reading/°C up to 121°C]
-40°F to 250°F [-40°C to 121]
Teflon ferrule maximum temperature is 200°F [93°C]
2000 psi [138 bar]
Teflon ferrule maximum pressure is 150 psig [10 bar(g)]
2″[50 mm] fixed
6″[150 mm] with variable insertion depth, compression fitting with Teflon or metal ferrule
Electronics
10 segment LED array, sequential lighting related to flow rate and flashing when trip point exceeded
Relay: SPDT, 1A @ 24 Vdc, 120 Vac Analog: 4-20 mA trending*
Serial: RS232C I/O
*500 ohm maximum load; user scalable, general purpose, uncalibrated output proportional to flow rate for trend monitoring or assignable to temperature; fault indication per NAMUR NE43 guidelines, user-selectable for high (>21.0mA) or low (<3.6mA) default
For linearized and calibrated analog outputs, see FCI’s line of thermal mass flow meter products
Two top-mounted buttons to program switch/trip point, zero and span setting, fail-safe, relay hysterisis and relay time delay; button operation may be user disabled to prevent unwanted changes; all set-up function are also user programmable via the RS232C serial port
- Trip Point Hysteresis Control: 0-100% of span
- Trip Point Time Delay: user settable for 0-65,000 seconds
24 Vdc (21.5 Vdc to 30Vdc); 2.5 watts maximum
-40°C to 160°F [-40°C to 71°C]
Enclosure/Housing
- Material: stainless steel body; aluminum end-cap/top with polyester overlay and clear, silicone sheath impact guard
Non-Ex Installations: IP65 IP66, IP67
FM, FMc approved: NEMA 4X
ATEX, IECEx approved: IP64
Agency Approvals
- FM, FMc: Nonincendive, Class I, Division 2, Groups A,B,C,D; Class II, Division 2, Groups E,F,G; Class III, T4@Ta=71°C, Type 4X
- ATEX, IECEx: Nonincendive for gas and dust, Zone 2; II 3 G Ex ec IIC T4 Gc; II 3 D Ex tc IIIC T81°C Dc; IP64
- EAC/TR CU: Pending. Contact FCI
- Other CE Mark, CRN, complies with Canadian electrical code requirement of ANSI/ISA 12.27.01-2011 as single seal device.
- IEC 61508 (SIL): SIL 2 Compliant, SFF 90%